Additional Specifications:
- Line Load reactor ambient operating temperature range is -40ºC to +50ºC.
- Impedance levels 3%, 5%
- Continuous Service Factor:
Reactors rated 1 to 750 Amps - 150% of rating
Reactors rated above 750 Amps - 125% of rating
- Overload Rating: 200% of rated for 30 minutes; 300% of rated for 1 minute
- Maximum switching frequency 20 kHz
- Maximum operating altitude, without derating
- Insulation System- Class N (200 Deg. C)
- Inductance Curve (Typical)
100% at 100% Current
100% at 150% Current
50% at 350% Current
- Inductance Tolerance +/- 10%
- Impregnation: High Bond Strength "solventless" Epoxy, 200 Deg C, UL94HB recognized
- Dielectric Strength: 3000V RMS (4243 Volts Peak)
- dv/dt Protection: Meets NEMA MG-1, Part 31 (Same as inverter duty motors)